Proficoud FAQ常见问题解答(持续添加)
1、There is no vaild private key on the device ...........
A:please reset token in proficloud
2、the error message"The device token cloud not be reset" happened when you reset token in proficloud.
A: you shouldn't reset the token twice in short time, otherwise it will occur this error . Please reboot the plcnext .
3、it shows the below error message when you add device in proficloud
A : please connect xuchuansen@phoenixcontact.com.cn to help you register this device in backend.
4、it shows the "MQTT error" in wbm
?
A : (1) please click "reset token" in proficloud front-end.
This action :
- resets the internal identification token
- revokes the device certificate
- allows the device to request new credential for 10min
(2)After a restart of the device, it schould connect again.
5、PLCnext reset后固件回到了1.1.0.23版本,無法通過wbm在線升級了,如下
1) 使用WinSCP 工具將下載的固件安裝后得到raucb 文件,將該文件上傳至PLC 中,上傳路徑:/opt/plcnext/
?2) 使用Putty 工具遠程登錄PLC,輸入系統密碼→輸入“sudo update-axcf2152”指令,首次使用會有警告,要求用戶權限,再次輸入密碼登錄即可執行升級命令。
?
?正確輸入命令后,系統重啟,原/opt/plcnext目錄下的固件會被自動刪除。整個升級過程大約
持續一分鐘。
6、The PLCnext keep the "connecting" status and loss the "Apply" button in bottom right corner
?A:可能由于配置的問題導致了證書的損壞,我們可以
- 手動刪除clientkey 目錄/opt/plcnext/projects/Default/Services/ProfiCloudV3/clientkey
- reset token in front-end,等待10分鐘
- 有時你也重啟一下PLCnext
7、Connection attempt failed. Next connection aaempt in 259 seconds
一種可能是網絡有問題,@yanglu遇到過這個問題
另一種是時間有問題,@wuchangnig遇到過,如果在log中看到如下錯誤,那一般是因為時間設置有問題,
8、The device is not registered in the cloud
?A: 你需要先將設備添加到某一個用戶的proficloud賬號中
9、您已經預訂了package,但是在服務中卻看不到,如下圖
A:您看一下上圖的橢圓框中的設備類型如果是unknown,那么有可能是設備reset token出現了問題,您可以重啟PLCnext來解決該問題
10、如何關閉plcnext的utc自動同步策略
vim?/etc/default/rcS 將utc=no
?11、Reboot PLCnext后外網的IP網絡不再可用,需要換一個外網網絡IP才行
因為linux會按順序監測網口,當第一個網口連接不上時,會重置所有的網口,因此要么將所有的網口都設置成外網的同一個IP,要么將第一個網口作為對外連接的網口?
總結
以上是生活随笔為你收集整理的Proficoud FAQ常见问题解答(持续添加)的全部內容,希望文章能夠幫你解決所遇到的問題。
- 上一篇: python爬取51job网